E6581301
M-2
13
(Continued)
Error
code
Description Possible causes Remedies
QN Motor overload
The V/f parameter is improperl
y
set.
•The motor is locked up.
•Low-speed operation is performed
continuously.
•An excessive load is applied to the
motor during operation.
•Check the V/f parameter setting.
•Check the load (operated machine).
•Adjust H to the overload that the motor can
withstand durin
g
operation in a low speed ran
g
e.
• Reduce the DC braking amount H and the
DC braking time H.
QNT
Dynamic
braking resistor
overload
•Rapid deceleration is operated.
•Dynamic braking is too large.
•Increase the deceleration time FGE.
•Increase the capacity of dynamic braking resistor
(wattage) and adjust PBR capacity parameter
RDER.
QR
Overvoltage
during
acceleration
The input volta
g
e fluctuates abnormall
y
.
(
1
)
The power suppl
y
has a capacit
y
of 500kVA or more.
(2)A power factor improvement
capacitor is opened and closed.
(3)A system using a thyrister is
connected to the same power
distribution line.
•A restart signal is input to the
rotating motor after a momentary
stop, etc.
•Insert a suitable input reactor.
•Use WX (Auto-restart) and WXE (Regenerative
power ride-though control).
QR
Overvoltage
during
deceleration
The deceleration time
FGE
is too
short (regenerative energy is too
large).
•The d
y
namic brakin
g
resistor has a
considerably large resistance.
RD
(
D
y
namic brakin
g
resistor
)
is OFF.
Overvolta
g
e limit operation H
is OFF.
The input volta
g
e fluctuates abnormall
y
.
(
1
)
The power suppl
y
has a capacit
y
of 500kVA or more.
(2)A power factor improvement
capacitor is opened and closed.
(3)A system using a thyrister is
connected to the same power
distribution line.
•Increase the deceleration time FGE.
•Install a dynamic braking resistor.
•Decrease dynamic braking resistance. (Also reset
the RDT.)
•Set dynamic braking mode parameter RD
properly.
•Set overvolta
g
e limit operation H properl
y
.
•Insert a suitable input reactor.
QR
Overvoltage
during fixed
speed operation
•The input voltage fluctuates
abnormally.
(
1
)
The power suppl
y
has a capacit
y
of 500kVA or more.
(2)A power factor improvement
capacitor is opened and closed.
(3)A system using a thyrister is
connected to the same power
distribution line.
•The motor is in a regenerative
state because the load causes the
motor to run at a frequency higher
than the inverter output frequenc
y
.
•Insert a suitable input reactor.
•Install a dynamic braking resistor.
*QV Overtorque
•Overtorque reaches to a detection
level during operation.
•Stall prevention operation was
performed continuously for a
length of time longer than that set
with H.
•Check system error.
• Check whether the motor is overloaded or the
brake is engaged.
*WE
Low current
operation
•The output current decreased to a
low-current detection level during
operation.
•Check the suitable detection level for the system
(H).
•Make a service call if the setting is correct.
*WR
Undervoltage
(main circuit)
•The input voltage (in the main
circuit) is too low.
•Momentary power failure occurs
because undervoltage continues
lon
g
er than undervolta
g
e detection
time H.
•Check the input voltage.
•To cope with a momentary stop due to
undervoltage, enable WXE (Regenerative power
ride-through control), WX (auto-restart control),
and H (Undervoltage detection time).
G Emer
g
enc
y
stop
•Inverter is stopped by panel
operation during automatic or
remote operation.
•A stop command (input terminal
function:  or ) is issued by
an external control device.
•Reset the inverter.
*Presence or absence of parameter trip can be selected.