Before making a service call
- Trip information and remedies
13.1 Trip causes/warnings and remedies
When a problem arises, diagnose it in accordance with the following table.
If it is found that replacement of parts is required or the problem cannot be solved by any remedy described in the table,
contact your supplier.
[Trip information]
Error
code
Description Possible causes Remedies
QE
*QER
Overcurrent
during
acceleration
•
The acceleration time
CEE
is too short.
•The V/f setting is improper.
•A restart signal is input to the
rotating motor after a momentary
stop, etc.
•A special motor (e.g. motor with a
small impedance) is used.
•
Manual torque boost value
XD
is lar
e.
•Increase the acceleration time CEE.
•Check the V/f parameter setting.
•Use WX(Auto-restart) and WXE (Regenerative
power ride-though control).
•Increase the carrier frequency EH.
•Decrease XD setting value.
• Decrease H (stall prevention level) to 130
as a guide.
• Increase EH
carrier frequenc
settin
value if it
is set at lower value (2kHz or less).
QE
*QER
Overcurrent
during
deceleration
•The deceleration time FGE is too
short. (in deceleration)
•Increase the deceleration time FGE.
QE
*QER
Overcurrent
during fixed
speed
•The load fluctuates abruptly.
•The load is in an abnormal
condition.
•Reduce the load fluctuation.
•Check the load (operated machine).
[Note] QER, QER,
QER originate from
causes other than those
mentioned above.
•
A main circuit elements is defective.
•Overheat protection is activated.
•Make a service call.
•Check operation of cooling fan.
•Check cooling fan control mode parameter
H.
*QEC
U-phase
arm
short-circuit
•A main circuit elements is defective
(U-phase).
•Make a service call.
*QEC
V-phase
arm
short-circuit
•A main circuit elements is defective
(V-phase).
•Make a service call.
*QEC
W-phase
arm
short-circuit
•A main circuit elements is defective
(W-phase).
•Make a service call.
QEN
loaded side
overcurrent at
start time
•The insulation of the output main
circuit or motor is defective.
•The motor has too small
impedance.
•Check the cables and wires for defective
insulation.
•Selection of short circuit detection at starting
parameter H.
QET
D
namic brakin
element
overcurrent
(200V-55kW or
larger, 400V-
90kW or lar
er
•PB-PC/+ circuit is shorted.
•A resistor with resistance smaller
than the minimum allowable
resistance is connected.
•Parameter RD was set to or
without connecting regenerative
brake or with wire disconnected
(with dynamic braking).
•Check the impedance wirin
for the resistor, etc.
•Make a service call.
•Check if regenerative brake is connected.
•If regenerative brake is not necessary, set
parameter RD to .
QJ Overheating
•The cooling fan does not rotate.
•The ambient temperature is too
high.
•The vent is blocked up.
•A heat generating device is
installed close to the inverter.
•The thermistor in the unit is
disconnected.
•Restart the operation b
resettin
the inverter afte
it has cooled down enough.
•The fan requires replacement if it does not rotate
during operation.
•Secure sufficient space around the inverter.
•Do not place any heat generating device near the
inverter.
•Make a service call.
QJ
Thermal trip
stop command
from external
device
• An input signal is impressed at
control input terminal PTG for
optional add-on cards.
•A thermal trip command (input
terminal function: or ) is
issued by an external control
device.
• The motor is overheated, so check whether the
current flowing into the motor exceeds the rated
current.
QN
Inverter
overload
•Rapid acceleration is operated.
•The DC braking amount is too
large.
•The V/f setting is improper.
•A restart signal is input to the
rotating motor after a momentary
stop, etc.
•The load is too large.
•Increase the acceleration time CEE.
•Reduce the DC braking amount H and the
DC braking time H.
•Check the V/f parameter setting.
•Use WX
Auto-restart
and WXE
Re
enerative
power ride-though control).
•Use an inverter with a larger rating.
* In the event one of the error codes QER to QER and QEC to QEC appears, in which case a main circuit
component has most probably failed, the only way to reset the inverter is to turn power off and back on.
(Continued overleaf)