Toshiba Tosvert VF-AS1 Bedienungsanleitung Seite 106

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 312
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 105
E6581301
E-40
5
Minimum resistance of connectable braking resistors
The minimum allowable resistance values of the externally connectable braking resistors are listed in the table
below.
Do not connect braking resistors with smaller resultant resistance than the listed minimum allowable resistance
values.
(For 200kW or greater models, a dynamic braking resistor drive unit (optional separate unit) is needed.)
200V Class 400V Class
Inverter
Related output capacity
(kW)
Resistance of
standard option
Minimum allowable
resistance
Resistance of
standard option
Minimum allowable
resistance
0.4 200 50 ––
0.75 200 50 200 60
1.5 75 35 200 60
2.2 75 25 200 60
3.7/4.0 40 16 160 40
5.5 20 11 80 30
7.5 15 8 60 30
11 10 5 40 20
15 7.5 5 30 20
18.5 7.5 5 30 15
22 3.3 3.3 15 13.3
30 3.3 2.5 13.3 10
37 2 1.7 8 6.7
45 2 1.7 8 5
55 2 1.7 8 5
75 1.7 1.3 8 3.3
90 3.7 2.5
110 3.7 1.9
132 3.7 2.5
160 3.7 1.3
200 1.9 1
220 1.9 1
280 1.4 1
355
400
500
Seitenansicht 105
1 2 ... 101 102 103 104 105 106 107 108 109 110 111 ... 311 312

Kommentare zu diesen Handbüchern

Keine Kommentare