E6581301
F-61
6
6.33.16 Regenerative power ride-through control level
H : Regenerative power ride-through control level
• Function
This parameter is used to set the operation level of the regenerative power ride-through control and the
deceleration stop. (Refer to Section 5.18.2.)
Title Function Adjustment range Default setting
H Regenerative power ride-through control level ~%
Note: Set this parameter at a value of H+5% or more. Or the braking time of regenerative power ride-though
control could be extremely shorter. This setting is not necessary if
H is set to (auto mode).
6.33.17 Braking answer waiting time
H : Braking answer waiting time
• Function
This parameter is used to set the waiting time for answer from system (Input terminal function setting:
System supporting sequence (BA: Braking answer
,
)). After start of operation, if no answer is
received in set time (
H
), the inverter trips (
G
).
Title Function Adjustment range Default setting
H Braking answer waiting time
:Disabled
~ sec.
6.33.18 VI/II analog input wire breakage detection level
H : VI/II analog input wire breakage detection level
• Function
The inverter will trip if the VI/II value remains below the specified value for 0.3 seconds or moreThe
message “
G
” is displayed.
H=: Disabled
・・・・・ The detection function is disabled.
H=~
・・・・・・・ The inverter will trip if the VI/II value remains below the specified value for 0.3
seconds or more.
Title Function Adjustment range Default setting
H VI/II analog input wire breakage detection level
:None
~%