H 0570
Preset speed operation frequency
10 operation mode
Ditto 1/1 0 Disabled ●/● - ●●5. 12
H 0571
Preset speed operation frequency
11 operation mode
Ditto 1/1 0 Disabled ●/● - ●●5. 12
H 0572
Preset speed operation frequency
12 operation mode
Ditto 1/1 0 Disabled ●/● - ●●5. 12
H 0573
Preset speed operation frequency
13 operation mode
Ditto 1/1 0 Disabled ●/● - ●●5. 12
H 0574
Preset speed operation frequency
14 operation mode
Ditto 1/1 0 Disabled ●/● - ●●5. 12
H 0575
Preset speed operation frequency
15 operation mode
Ditto 1/1 0 Disabled ●/● - ●●5. 12
[24] Protection functions [1/3]
Vector control
Title
Communi
cation
No.
Function Adjustment range
Minimum
settin
unit
Panel/Communi
cation)
Default
settin
Write durin
runnin
Speed
control
Torq ue
control
PM
control
V/f Constan
Reference
H 0601 Stall prevention level 0~164%, 165:Deactivated 1/1 150 Enabled ●/● - ●●6. 33. 1
H 0602
Inverter trip record retention
selection
0:Clear when power is turned off
1:Retain even after power is turned off
1/1 0 Enabled ●/●●/●●●6. 33. 2
H 0603 Emergency stop
0:Coast stop
1:Deceleration stop
2:Emergency DC braking
3:Deceleration stop (deceleration 4)
1/1 0 Disabled ●/●●/●●●6. 33. 3
H 0604
Emergency DC braking control
time
0.0~20.0 sec. 0.1/0.1 1.0 Enabled ●/●●/●●●6. 33. 3
H 0605
Output phase failure detection
selection
0:Deselect
1:At starting (only one time after power is turned
on)
2:At starting (each time power is turned on)
3:During operation
4:At starting + during operation
5:Output cut-off detection enabled
1/1 0 Disabled ●/●●/●●●6. 33. 4
H 0606 OL reduction startin
frequenc
0.0~30.0Hz 0.1/0.01 6.0 Enabled ●/●●/●●●5. 14
H 0607 Motor 150%-overload time limit 10~2400 sec. 1/1 300 Enabled ●/●●/●●●5. 14
H 0608
Input phase failure detection
mode selection
0:Deselect
1:Select
1/1 1 Disabled ●/●●/●●●6. 33. 7
H 0609
Low current detection current
hysteresis width
1~20% 1/1 10 Enabled ●/●●/●●●6. 33. 8
H 0610 Low current trip selection 0:No trip, 1:Trip 1/1 0 Enabled ●/●●/●●●6. 33. 8
H 0611 Low current detection current 0~100% 1/1 0 Enabled ●/●●/●●●6. 33. 8
H 0612 Low current detection time 0~255 sec. 1/1 0 Enabled ●/●●/●●●6. 33. 8