[28] Communication function [2/4]
Vector control
Title
Communi
cation
No.
Function Adjustment range
Minimum
settin
unit
Panel/Communi
cation)
Default
settin
Write durin
runnin
Speed
control
Torq ue
control
PM
control
V/f Constan
Reference
H 0826
Inverter-to-inverter
communication setting (4-wire
RS485)
0:Slave
issues a 0Hz command if somethin
oes
wrong with the master)
1:Slave (continues operation if something goes
wrong with the master)
2:Slave (trips for emergency stop if something
goes wrong with the master)
3:Master (sends a frequency command)
4:Master (sends an output frequency)
5:Master (sends a torque command)
6:Master (sends an output torque command)
1/1 0 Enabled ●/●●/●●●6. 38. 1
H 0829
Protocol selection (4-wire
RS485)
0:TOSHIBA
1:MODBUS
1/1 0 Enabled ●/●●/●●●6. 38. 1
H 0830
Communication option
DeviceNet
PROFIBUS
settin
1
0~7 1/1 0 Enabled ●/●●/●●● *1
H 0831
Communication option
DeviceNet
PROFIBUS
settin
2
0000~HHHH 1/1 0000 Enabled ●/●●/●●● *1
H 0832
Communication option
DeviceNet
PROFIBUS
settin
3
0000~HHHH 1/1 0000 Enabled ●/●●/●●● *1
H 0833
Communication option
DeviceNet
PROFIBUS
settin
4
0000~HHHH 1/1 0000 Enabled ●/●●/●●● *1
H 0834
Communication option
DeviceNet
PROFIBUS
settin
5
0000~HHHH 1/1 0000 Enabled ●/●●/●●● *1
H 0835
Communication option
DeviceNet
PROFIBUS
settin
6
0000~HHHH 1/1 0000 Enabled ●/●●/●●● *1
H 0836
Communication option
DeviceNet
PROFIBUS
settin
7
0000~HHHH 1/1 0000 Enabled ●/●●/●●● *1
H 0841
Communication option
DeviceNet
PROFIBUS
settin
8
0000~HHHH 1/1 0000 Enabled ●/●●/●●● *1
H 0842
Communication option
DeviceNet
PROFIBUS
settin
9
0000~HHHH 1/1 0000 Enabled ●/●●/●●● *1
H 0843
Communication option
DeviceNet/
PROFIBUS) setting 10
0000~HHHH 1/1 0000 Enabled ●/●●/●●● *1
H 0844
Communication option
DeviceNet/
PROFIBUS) setting 11
0000~HHHH 1/1 0000 Enabled ●/●●/●●● *1
*1: ⇒ For details, refer to Instruction Manual (E6581281, E6581343) specified in Section 6.41.