E6581301
E-41
5
5.20 Standard default setting
V[R : Default setting
[Parameter setting]
Title Function Adjustment range Default setting
V[R Factory default setting
: –
:50Hz default setting
:60Hz default setting
:Factory default setting
:Trip clear
:Cumulative operation time cleared
:Initialization of type information
:Save user-defined parameters
:Reset of user-defined parameters
:Cumulative fan operation time record clear
:Acceleration/deceleration time setting
0.01 sec.~600.0 sec.
:Acceleration/deceleration time setting 0.1
sec.~6000 sec.
+This parameter is used to change the settings of other parameters. Therefore, is always displayed.
+V[R cannot be set during the inverter operating. Always stop the inverter first and then program.
+ When parameter V[R is invoked, the value set previously is displayed on the left side of the parameter.
[Programmed value]
50Hz default setting (V[R=)
Setting V[R at causes all the following parameters to be set for operation using a base frequency of 50Hz.
(This does not change the settings of any other parameters.)
• Maximum frequency HJ : 50Hz • VI/II input point 2 frequency CKH : 50Hz
• Base frequency 1 XN : 50Hz • RR/S4 input point 2 frequency CXH : 50Hz
• Base frequency 2 H : 50Hz • RX input point 2 frequency H : 50Hz
• Base frequency 3 H : 50Hz • AI1 input point 2 frequency H : 50Hz
• Base frequency 4 H : 50Hz • AI2 input point 2 frequency H : 50Hz
• Upper limit frequency WN : 50Hz •
RP/high-speed pulse input point 2 frequency
H : 50Hz
• Forward speed limit input level H : 50Hz • PID deviation upper limit H : 50Hz
• Reverse speed limit input level H : 50Hz • PID deviation lower limit H : 50Hz
•
Commercial power/inverter switching frequency
H : 50Hz • Process upper limit H : 50Hz
• Point 2 frequency H : 50Hz • PID output upper limit H : 50Hz
•
Automatic light-load high-speed operation frequency
H : 50Hz • Motor rated revolutions (motor name plate)
H
:
1410min-1
60Hz default setting (V[R=)
Setting V[R at causes all the following parameters to be set for operation using a base frequency of 60Hz.
(This does not change the settings of any other parameters.)
• Maximum frequency HJ : 60Hz • VI/II input point 2 frequency CKH : 60Hz
• Base frequency 1 XN : 60Hz • RR/S4 input point 2 frequency CXH : 60Hz
• Base frequency 2 H : 60Hz • RX input point 2 frequency H : 60Hz
• Base frequency 3 H : 60Hz • AI1 input point 2 frequency H : 60Hz
• Base frequency 4 H : 60Hz • AI2 input point 2 frequency H : 60Hz
• Upper limit frequency WN : 60Hz •
RP/high-speed pulse input point 2 frequency
H : 60Hz
• Forward speed limit input level H : 60Hz • PID deviation upper limit H : 60Hz
• Reverse speed limit input level H : 60Hz • PID deviation lower limit H : 60Hz
•
Commercial power/inverter switching frequency
H : 60Hz • Process upper limit H : 60Hz
• Point 2 frequency H : 60Hz • PID output upper limit H : 60Hz
•
Automatic light-load high-speed operation frequency
H : 60Hz • Motor rated revolutions (motor name plate)
H
:
1710min-1
•Function
This parameter is to set two or more parameters at a time for different commands. Using this parameter, all
parameters can be also return to their respective default settings by one operation, and save or set specific
parameters individually.