[28] Communication function [3/4]
Vector control
Title
Communi
cation
No.
Function Adjustment range
Minimum
settin
unit
Panel/Communi
cation)
Default
settin
Write durin
runnin
Speed
control
Torq ue
control
PM
control
V/f Constan
Reference
H 0845
Communication option
DeviceNet/
PROFIBUS) setting 12
0000~HHHH 1/1 0000 Enabled ●/●●/●●● *1
H 0846
Communication option
DeviceNet/
PROFIBUS) setting 13
0000~HHHH 1/1 0000 Enabled ●/●●/●●● *1
H 0850
Disconnection detection
extended time
0.0~100.0 sec. 0.1/0.1 0.0 Enabled ●/●●/●●● *1
H 0851
Inverter operation at
disconnection
0:Inverter stop, communication command,
frequency mode open (by EOQF, HOQF)
1:None (continued operation)
2:Deceleration stop
3:Coast stop
4:Network error (GTT trip)
5:Preset speed operation (by H setting)
1/1 0 Enabled ●/●●/●●● *1
H 0852
Preset speed operation
selection
0:None
1~15:Preset speed operation (by parameter
setting)
1/1 0 Enabled ●/●●/●●● *1
H 0853
Communication option station
address monitor
0~255 1/1 0 Enabled ●/●●/●●● *2
H 0854
Communication option speed
switch monitor
DeviceNet/CC-Link
0~255 1/1 0 Enabled ●/●●/●●● *2
H 0870 Block write data 1
0:Deselect
1:Command information 1
2:Command information 2
3:Frequency command
4:Terminal board output data
5:Communication analog data
1/1 0 Enabled ●/●●/●●●6. 38. 1
H 0871 Block write data 2 Ditto 1/1 0 Enabled ●/●●/●●●6. 38. 1
*1: ⇒ For details, refer to Instruction Manual (E6581281, E6581343) specified in Section 6.41.
*2: ⇒ For details, refer to Instruction Manual (E6581281, E6581343, E6581288) specified in Section 6.41.
Sensorless vector/vector with sensor (●:Effective, -:Ineffective)