u r.
^ (Terminal Selection Parameters)
Oh 3 J Output terminal selections @
Open collector output detection level
•ON* : open collector transistor ON
■OFF': open collector transistor OFF
Setting
value
Function
Detection level
Overcurrent pre-alarm
■ON' during overcurrent stall protection operation
■ON' when the output current reaches the setting value level of
51 L 1 in C r.P r , or 5 b L 2 in C r.F B
when using fundamental parameters #Z
(Same level as the blinking t alarm on the operating panel
LED)
IB
Inverter overload pre-alarm
'ON' when the cumulative trip amount of DL In (inverter
overload trip) is 50% or more of the trip level.
IB
Motor overload pre-alarm
■ON' when the cumulative trip amount of OL fit (motor
overload trip) is 50% or more of the trip level.
BO
Overheat pre-alarm
■ON' when heatsink temperature is 84°C or higher
Once 'ON', turns 'OFF' again when temperature drops to 80“C or
less
BB
Overvoltage pre-alarm
■ON' during overvoltage limit operation (OP stalO of DC main
circuit voltage.
200V system: approx. 370Vdc
400V system: approx. 740Vdc
(Same level as the blinking p alarm on the operating panel
LED)
BH
Undervoltage alarm
■ON' when main circuit DC voltage is below the following levels:
200V system: approx. 200Vdc
400V system: approx. 380Vdc
BB
Undercurrent alarm ■ON' when output current is lower than the setting value of
LL PC in C n.Pr and continues for longer than the
time set in L L P b •
BB
Overtorque alarm ■ON" when the torque current exceeds the setting value of
DbL in Br.Pr .
30
Braking resistor overload pre
alarm
■ON' when the OL r cumulative trip amount is 50% or more
of the trip level.
* The checking conditions for the following alarm outputs differ from each other as indicated:
Undervoltage alarm: Checked while running.
Undercurrent alarm: Checked during run command.
Overtorque alarm ; Constantly checked.
Note) During reset, all status alarms will enter the OFF state regardless of the operating conditions.
- 58 -