0 (Fundamental Parameters #2)
Function
Title
Adjustment range
Ftesolution
Default Pago
Maximum voltage frequency #2
———
---------
1
----
urLd ¡
25~400
■ 0.01/0.1 Hz
60.0
54
Maximum voltage #2
1 P 1
ulC 1
1
0~€00 (Note 1)
IV 200V system: 200V
400V system: 400V
54
Voltage boost #2
[
Ulbd j
i
1
j
0-30
0.1%
Depends
on inverter
rating
54
Electronic thermal protection level #2
fcHr-2 j
10-100%/A (Note 2)
1%/A 100.0
54
Stall protection #2
5tcг i
1
I
0; ON
1: OFF
0
54
54
0
Stall protection level #2
(current limit level
adjustment)
SfcLd i
1
1
1
I
10-215%/A
1%/A
150.0
Acceleration time #2
Deceleration time #2
I
d£Cd !
1
j
0.1-6000/0.01-600.0
0.1-6000/0.01-600.0
0.1/0.01 S
0.1/0.01 S
Depends
on inverter
rating
46
Acc/dec pattern #2
sc^г i
1
1
I
1
j
0: Linear
1: Self-adjusting
2: S-Pattern #1
3: S-Pattern #2
0
54
Acc/dec #1/#2 switching frequency
RddF i
0—max. frequency (FH) 0.1/0.01 Hz
0.0
52
r" O
r~
(Panel Control Parameters)
Function
Title
Adjustment range
Resolution
Default Page
Fonward/reverse
Fr- i
1
I
0: Reverse
1: Forward
1
Stop pattern selection
StPP !
1
]
0: Decelerated stop
1: Coast stop
0
Fundamental parameter switching
PtP i
1
1
1: Fundamental parameters #1 (V/F#1)
2: Fundamental parameters #2 (V/F#2)
1
54
Acc/dec #1/#2 selection
Pdd !
1
1
1: Acc/dec #1
2: Acc/dec #2
1
52
Panel reset selection
P^£S 1
1
1
0: Ail possible
1: OL only (fault ignore #1)
2: OU OCl. OC2, OC3 only (fault ignore #2)
0
53
Panel feedback control
PID
Speed Feedback
Drooping
PPbC i
1
1
1
1
1
_____________
L_
0: ON (valid when panel operation is
selected)
1: OFF (invalid when panel operation
is selected)
0
53
Note 1) 200V system: Internally limited to 255V.
400V system: Internally limited to 510V.
Note 2) Parameters with note ’A‘ shown in the Adjustment Range and Resolution columns will be displayed
in either percent or Amps depending on the setting of dSPC in
and uGci* • in C<"F are valid only when ciLSL in Cf-.f" is set to ’ ? *.
-107 -
Seitenansicht 112
1 2 ... 108 109 110 111 112 113 114 115 116 117 118 ... 148 149

Kommentare zu diesen Handbüchern

Keine Kommentare